Product Description
Description: DeviceNet CIO Module for use with 601-CS-D-P1
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 200 - 480 Vac |
Maximum Input Power | 10 |
Input AC Line Frequency (Hz) | 50 / 60 |
Output Form | SPDT |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac |
Full Load Amp Range (A) | 0.5 - 175 (direct); 176 - 800 (external CTs required) |
Repeat Accuracy (%) | Voltage: ±0.5% of nominal voltage; Current: ±1% (<175 A direct) |
Voltage Accuracy (%) | ±1% |
Current Accuracy (%) | ±3% (<100 A direct) |
Ground Fault Accuracy (%) | ±3% |
Surge Protection | IEC: 61000-4-5 Level 3 2 kV line-to-line; Level 4 4 kV line-to-ground |
Protection Class | IP20 (finger safe) |
Pollution Degree | 3 |
Communications Protocol | Modbus RTU |
Termination Type | Torque: 7 in-lbs |
Mounting Method | Surface mount (4 - #8 screws) or DIN rail mount |
Operating Temperature | -20° to 70°C (-4° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm) |
Series Features |
601-CS-D-P1 Series - Monitors a zero-sequence CT for high accuracy ground fault protection |
Series Description: The 601-CS-D-P1 series is a fully programmable, electronic, three-phase, power monitor designed to monitor three-phase systems. This unit has a single relay that can be configured as a general purpose network output or to trip on ground faults. The 601-CS-D-P1 monitors ground-fault current, phase currents, phase voltages, power factor, and frequency. The RS485MS-2W communications module allows the 601-CS-D-P1 to communicate using the Modbus RTU protocol. The Modbus connection can be used to monitor power parameters, set up the device or control the fault relay. A DeviceNet* communications I/O module (CIO-601CS-DN-P1) is also available. This CIO module only works with the 601-CS-D-P1 unit. It is used for sending the information from the 601-CS-D-P1 over a DeviceNet* network. It also provides I/O capabilities and the ability to set the parameters of the 601-CS-D-P1. The 601-CS-D-P1 includes a built-in display that offers a visual indication for programming and viewing real-time parameters for nominal voltage, voltage unbalance, current, current unbalance, ground-fault warning, ground-fault trip, and ground-fault motor acceleration. |
Series Applications: For monitoring a zero-sequence current transformer for ground-fault protection |
|