Product Description
Description: Load Sensor/self-powered/5-200A/fast-on terminals
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Maximum Input Power | Induced from AC conductor |
Input Current Range (A) | 5 - 200 Continuous |
Output Form | SPST - Form A |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac B300; General Purpose: 5 A @ 240 Vac |
Sensor Hole Size | 0.725 in diameter |
Pull-in Current (A) | 4.5 (typical); 7.0 (max) |
Termination Type | Torque: 3 in.-lbs.; Wire: 12 - 26 AWG; 0.25 in quick-connect fast-on terminals |
Mounting Method | Surface mount |
Operating Temperature | -20° to 70°C (-4° to 158°F) |
Storage Temperature (F/C) | -40° to 80°C (-40° to 176°F) |
Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
Dimensions | 2.7 H x 1.13 W x 2.5 D in. (68.6 x 28.7 x 63.5 mm) |
Series Features |
LSRX / LSRX-C SERIES - Self-powered load sensor, low-cost proof relay |
Series Description: The LSRX/LSRX-C Series are AC current sensors designed to energize the output contact whenever 4.5 Amps or greater is present. The LSRX/LSRX-C Series is used commonly as an AC current proof relay to indicate if a motor is operating. It can also be used to interlock fans, compressors and motors; to indicate equipment status such as feed rates, tool wear, loss of prime on pumps, mixer viscosity and all types of current sensing conditions or to stage pump motors, chillers, or other machinery. This device combines a current transformer (CT), transducer and high current output relay together to switch alarm circuits, contactors and most resistive or inductive loads. The LSRX/LSRX-C Series can perform the function of an auxiliary contact, yet has the advantages of universal application and isolation. |
|