Product Description
Description: Load Sensor/115V/2-100A/20-turn pot
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage (V) | 115 Vac |
Input Current Range (A) | 0.5 - 135 continuous |
Output Form | SPDT |
Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A |
Sensor Hole Size | 0.725 in diameter |
Termination Type | Torque: 7 in.-lbs.; Wire: 12 - 24 AWG |
Mounting Method | Four #6 screws 3/4 in in length |
Operating Temperature | -20° to 70°C (-4° to 158°F) |
Dimensions | 1.67 H x 2.3 W x 3.56 D in. (42.4 x 58.4 x 90.4 mm) |
Series Features |
LSR-XXX SERIES - Load sensor |
Series Description: The LSR-xxx Series load sensors use current levels to determine feed rates, tool wear, loss of prime on pumps, mixer viscosity and all types of overload and underload conditions. They may also be used to stage pump motors, chillers and other machinery. These devices combine a current transformer (CT) with Form C (SPDT) relay contacts to switch alarm circuits, contactors or any resistive or inductive load. One simple screwdriver adjustment will calibrate the sensor for all single- phase or 3-phase applications up to 100hp. |
|