Product Description
Description: ALT Relay/95-120V/11-Pin Plug-in/1 input
| Product Information | Resources |
|
| Specifications |
| Product Attribute | Attribute Value |
| Input Voltage (V) | 95 - 120 Vac |
| Maximum Input Power | 5 |
| Input AC Line Frequency (Hz) | 50 / 60 |
| Output Form | DPDT |
| Output Load Rating (VA) | Pilot Duty: 480 VA @ 240 Vac; General Purpose: 10 A @ 240 Vac |
| Debounce Time Delay (s) | 1 |
| Termination Type | Torque: 12 in-lbs.; 12 - 22 AWG solid or stranded |
| Mounting Method | DIN rail or surface mount (plug-in to OT11-PC socket) |
| Operating Temperature | -40° to 70°C (-40° to 158°F) |
| Humidity | 10 - 95% non-condensing per IEC 68-2-3 |
| Dimensions | 1.75 H x 2.38 W x 4.13 D in. (44.5 x 60.3 x 104.8 mm) |
| Series Features |
| ALT-XXX-1-SW / ALT-XXX-3-SW SERIES - Alternating Relay |
| Series Description: The ALT-xxx-1-SW/ALT-xxx-3-SW Series are used to alternate between two loads and are commonly used in duplex pump-up and pump-down applications to balance the runtime of both pumps. The ALT relays have a built-in debounce time delay that prevents the relay from changing state if the float momentarily bounces, and they have a built-in switch to manually force a specific load (pump) to operate each time the input float closes. This is helpful when performing periodic maintenance or pump repair. |
|