| Manufacturer | Startco / Littelfuse |
| Manufacturer Product Number | SB6100-110-0 |
| Description | Ground Fault Circuit Breaker; EGFPD; 240 V; Open-Chassis Model |
| Datasheet | Download Datasheet |
The Littelfuse Startco SB6100-110-0 is a Shock Block special-purpose ground-fault circuit interrupter: an EGFPD unit rated 100 A (continuous) at 240 V, open-chassis version.
It protects people from electric shock on industrial equipment and circuits beyond the reach of standard GFCI receptacles and breakers: it trips on ground-fault current above its trip level and monitors the ground connection to the load.
Trip level: 6, 10-100 mA in increments of 10 (selectable). Trip time: inverse time trip curve (UL 943); minimum trip time 20 ms. Phases: 3-phase, 3-wire (no neutral), 60 Hz. Short-circuit current rating: 50,000 A. Ground monitoring: load-ground-connection monitor optional (recommended) for EGFPD; 1N5339B termination device factory-installed at the GC terminal, remains installed if monitoring is not required; GC-loop trip resistance 38 ± 2 Ω; open-circuit voltage 12 vdc; nominal loop current 30 mA. Output: auxiliary contact, normally open (N.O.), follows the state of the internal contactor; UL rating 4 A resistive 220/240 vac, 0.3 A resistive 250 vdc.
Enclosure: None (open chassis, UL-recognized for installation in a suitable enclosure; tamper-indicating labels installed). Operating temperature –35 °C (–31 °F) to + 40 °C (104 °F), up to + 66 °C (151 °F) with derating. Size: H 455.0 mm (17.9”); W 340.7 mm (13.4”); D 174.9 mm (6.9”).
Approvals: cURus Recognized Component UL 943/UL 1053 (open-chassis); CSA certified (C22.2 No. 144-M91, Class 4812-02); UL 1998 compliant (revision 01 or higher).
| Category | |
| Manufacturer | Startco / Littelfuse |
| Model | SB6100 |
| Part Status | Discontinued |
| GFCI Class | EGFPD |
| Voltage Rating | 240 V |
| Phases | 3-phase, 3-wire (no neutral), 60 Hz |
| Current Rating | 100 A (continuous); AC-1 100 A; AC-3 75 A |
| Trip Level | 6, 10-100 mA in increments of 10 (selectable) |
| Trip Time | Inverse time trip curve (UL 943); minimum trip time 20 ms |
| Short Circuit Rating | 50,000 A |
| Enclosure Material | Open-Chassis Model |
| Enclosure Rating | None (open chassis, UL-recognized for installation in a suitable enclosure; tamper-indicating labels installed) |
| Ground Monitoring | Load-ground-connection monitor optional (recommended) for EGFPD; 1N5339B termination device factory-installed at the GC terminal, remains installed if monitoring is not required; GC-loop trip resistance 38 ± 2 Ω; open-circuit voltage 12 Vdc; nominal |
| Contact Configuration | Auxiliary contact, Normally Open (N.O.), follows the state of the internal contactor; UL rating 4 A resistive 220/240 Vac, 0.3 A resistive 250 Vdc |
| Operating Temperature | –35 °C (–31 °F) to + 40 °C (104 °F), up to + 66 °C (151 °F) with derating |
| Dimensions | H 455.0 mm (17.9”); W 340.7 mm (13.4”); D 174.9 mm (6.9”) |
| Approvals | cURus Recognized Component UL 943/UL 1053 (open-chassis); CSA certified (C22.2 No. 144-M91, Class 4812-02); UL 1998 compliant (revision 01 or higher) |