Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Startco / Littelfuse |
| Manufacturer Product Number | NGRUS354 |
| Description | Neutral Grounding Resistor; 2 A; Continuous |
| Datasheet | Download Datasheet |
The Littelfuse Startco NGRUS354 is a neutral grounding resistor system for 600 V line-to-line, 347 V line-to-neutral systems, limiting ground-fault current to 2 A (continuous rating).
A neutral grounding resistor holds the current of a line-to-ground fault to a safe, known value, so a resistance-grounded system can keep running on the first fault while the monitor finds it.
Supplied as: Neutral Grounding Resistor System (NGR, current transformer and sensing resistor in a NEMA 3R enclosure). Resistance: 173.5 Ω (+/- 10 % resistance). Monitor: SE-325. Current transformer: CT200. Sensing resistor: ER-600VC.
Enclosure: NEMA 3R, galvanized steel, NEMA 3R. Finish: powder coated. Insulation level: 11 KV BIL. Temperature rise: 385 °C (725 °F). Seismic bracing: included. Size: Refer to dimensions drawings (no drawing printed for this part number).
Approvals: cULus or CSA at customer request.
| Category | |
| Manufacturer | Startco / Littelfuse |
| Model | NGRUS |
| Product Type | Neutral Grounding Resistor System (NGR, current transformer and sensing resistor in a NEMA 3R enclosure) |
| System Voltage | 600 V line-to-line, 347 V line-to-neutral |
| Let-Through Current | 2 A |
| Resistance | 173.5 Ω |
| Time Rating | Continuous |
| Tolerance | +/- 10 % resistance |
| Current Transformer | CT200 |
| Sensing Resistor | ER-600VC |
| Monitor | SE-325 |
| Enclosure Style | NEMA 3R, galvanized steel |
| Enclosure Rating | NEMA 3R |
| Finish | Powder coated |
| Insulation Level | 11 KV BIL |
| Temperature Rise | 385 °C (725 °F) |
| Seismic Bracing | Included |
| Altitude | 0–2000 masl |
| Dimensions | Refer to dimensions drawings (no drawing printed for this part number) |
| Approvals | cULus or CSA at customer request |