| Manufacturer | Startco / Littelfuse |
| Manufacturer Product Number | PGR-8800-00 |
| Description | Arc-Flash Relay; <1 ms |
| Datasheet | Download Datasheet |
The Littelfuse Startco PGR-8800-00 is an arc-flash relay.
It watches switchgear, motor control centres and panelboards for the light of an arcing fault and trips the upstream breaker within milliseconds, limiting the incident energy an arc flash can release. Detection: light and current; optical trip settings 9–25 klux, 800 μs-20 s; current trip setting (A) programmable. Sensors: 6 per unit (built-in sensor usable as a seventh); up to 24 with four linked units. Sensor inputs: PGA-LS10 point sensors and PGA-LS20/PGA-LS30 fiber-optic sensors; built-in sensor; phase-CT inputs (5-A-secondary phase CTs per circuit diagram). Trip time: <1 ms.
Supply: 100–240 V ac, 14–48 V dc, and 110–250 V dc; ability to charge and run off an external, user-supplied 24 V dc battery.
Outputs: trip coil contact: solid-state 24–300 V dc/24–300 V ac IGBT, selectable fail-safe or non-fail-safe; indication contacts: Form C and status outputs (fail-safe). Communications: USB interface; Modbus. Indication: 18 LEDs (module and I/O state); LEDs on each sensor.
Mounting: surface, DIN (with D0050 adapter clips). Size: H 130 mm (5.1”); W 200 mm (7.9”); D 54 mm (2.1”).
Approvals: UL, CE, CSA, RCM, FCC, DNV type approval, ABS type approval; cULus UL508 E348169; CSA LR 62897.
| Category | |
| Manufacturer | Startco / Littelfuse |
| Model | PGR-8800 |
| Monitoring Function | Microprocessor-based protection relay that uses light sensors to rapidly detect an arc and then trip a circuit breaker; current-constrained arc-flash protection and programmable definite-time overcurrent |
| Detection | Light and current; Optical Trip Settings 9–25 klux, 800 μs-20 s; Current Trip Setting (A) Programmable |
| Number of Sensors | 6 per unit (built-in sensor usable as a seventh); up to 24 with four linked units |
| Sensor Inputs | PGA-LS10 point sensors and PGA-LS20/PGA-LS30 fiber-optic sensors; built-in sensor; phase-CT inputs (5-A-secondary phase CTs per circuit diagram) |
| Trip Delay | <1 ms |
| Input Voltage | 100–240 V ac, 14–48 V dc, and 110–250 V dc; ability to charge and run off an external, user-supplied 24 V dc battery |
| Contact Configuration | Trip coil contact: solid-state 24–300 V dc/24–300 V ac IGBT, selectable fail-safe or non-fail-safe; Indication contacts: Form C and status outputs (fail-safe) |
| Communication Protocol | USB interface; Modbus |
| Status Indicator | 18 LEDs (module and I/O state); LEDs on each sensor |
| Mounting Type | Surface, DIN (with D0050 adapter clips) |
| Dimensions | H 130 mm (5.1”); W 200 mm (7.9”); D 54 mm (2.1”) |
| Approvals | UL, CE, CSA, RCM, FCC, DNV type approval, ABS type approval; cULus UL508 E348169; CSA LR 62897 |
| UL File Number | E348169 |