Product Description
Littelfuse Industrial Business Unit KLDR Series Fuse; Requires Holder; 200kA AC, 20kA DC; CC;6.25A;600 VAC;300 VDC; Slow Blow; 5AG, 10mm x 38mm (Midget)
Cylindrical Fuse • Mounting Type: Requires Holder • Fuse Type: Cartridge • Current Rating (Amps): 6.25A • Voltage Rating - AC: 600 VAC • Voltage Rating - DC: 300 VDC • Response Time: Slow Blow • Class: CC • Breaking Capacity @ Rated Voltage: 200kA AC, 20kA DC • Package / Case: 5AG, 10mm x 38mm (Midget)
Product Information
| Manufacturer | Littelfuse Industrial Business Unit |
| Product Category | Fuses |
| Product Sub Category | Cylindrical Fuse |
| Series | KLDR Series |
| Catalog Part Number | KLDR004.HXP |
| Ordering Part Number | KLDR004.HXP |
Specifications
| Product Attribute | Attribute Value |
|---|---|
| Mounting Type | Requires Holder |
| Fuse Type | Cartridge |
| Current Rating (Amps) | 4A |
| Voltage Rating - AC | 600 VAC |
| Voltage Rating - DC | 300 VDC |
| Response Time | Slow Blow |
| Applications | Transformer Protection |
| Class | CC |
| Approval Agency | CE, CSA, UL |
| Breaking Capacity @ Rated Voltage | 200kA AC, 20kA DC |
| Package / Case | 5AG, 10mm x 38mm (Midget) |
| Size / Dimension | 0.406" Dia x 1.500" L (10.30mm x 38.10mm) |
Series Features
Class CC Fuses KLDR Series 600 V ac • 300 V dc • Time-Delay • 1⁄10 –30 A
Series DescriptionKLDR Series time-delay fuses are designed to protect control transformers, solenoids, and similar inductive components with high-magnetizing currents during the first half-cycle. These small-sized fuses provide excellent protection of motor branch circuits containing IEC or NEMA-rated motor controllers or contactors. The KLDR Series fuses closely match most control power transformer characteristics, which permits them to be sized in accordance with the latest revisions of UL 508 (Industrial Control) and UL 845 (Motor Control Centers).
- Current-limiting: Reduces damage caused by heating and magnetic effects of short-circuit currents
- Short-circuit protection: Improves safety with faster response times to fault currents
- Rejection capability: Prevents use of fuses with lower interrupting ratings or voltage when used with corresponding fuse holders
- Time-delay: Allows for a temporary current surge for a short period of time without blowing
Transformer and solenoid protection