Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Kanson / ISSC |
| Manufacturer Product Number | 1213-1-B-B-OP2 |
| Description | Resistance Sensitive Detectors; Adjustable 10-110 Ohm; 120 VAC; Base mount |
| Datasheet | Download Datasheet |
The Kanson / ISSC 1213-1-B-B-OP2 is a resistance sensitive detectors with 1 N.O., 1 N.C., electrically isolated output and rated 10 A @ 240 VAC maximum, driven by a 120 VAC input.
It controls the level of a conductive liquid, low resistance sensitive, single control point to terminals e-f the tank.
It switches between a high and a low probe, so the gap between them sets how far the level travels before the pump runs again.
The setpoint covers Adjustable 10-110 Ohm between probe and common, so it is the conductivity of the liquid that decides the part.
The probe is pulsed with 2 VDC max. open circuit; 2.0 mA max. short circuit current rather than held at a steady potential, which is what stops it electroplating away in service.
It has Base mounting and Terminal block on face of unit terminals.
| Category | |
| Manufacturer | Kanson / ISSC |
| Control Function | Low resistance sensitive, single control point (terminals E-F) |
| Number of Probes | 2 |
| Sensitivity Range | Adjustable 10-110 Ohm |
| Probe Voltage | 2 VDC max. open circuit; 2.0 mA max. short circuit current |
| Input Voltage | 120 VAC |
| Input Operating Range | +/-15% of nominal |
| Rated Power | 10 VA maximum |
| Output Type | Electromechanical relay |
| Contact Configuration | 1 N.O., 1 N.C., electrically isolated |
| Output Rating | 10 A @ 240 VAC maximum |
| Operating Temperature (°C) | 0...+50 |
| Mounting Type | Base mount |
| Termination Style | Terminal block on face of unit |
| Housing Material | Metal |
| Dimensions | 2.875 x 3.06 in (73.0 x 77.7 mm), depth 4.25 in (108.0 mm) (same as 1214) |