Description: Alternating / Sequencing Relay • Alternating / Sequencing Relay • Operating Voltage: 120 VAC • Contact Configuration: 1C SPDT • Contact Current: 10 Amp • Mounting: Surface Mount • Termination: 1/4" Quick Connect Terminals • Lockout Option: Rotary Switch • Features: None
| Product Information | Resources |
| |
| Specifications |
| Product Attribute | Attribute Value |
| Operating Voltage | 120 VAC |
| Contact Configuration | 1C SPDT |
| Contact Current | 10 Amp |
| Mounting | Surface Mount |
| Termination | 1/4" Quick Connect Terminals |
| Lockout Option | Rotary Switch |
| Features | None |
| Tolerance | ±20% of Nominal |
| Frequency | 50 - 60 Hertz |
| Electrical Life | Full Load - 100,000 Operations |
| Mechanical Life | 10,000,000 Operations |
| Transient | ±1500 Volts for 150 Microseconds |
| Dielectric Breakdown | 1500 Volts RMS Minimum |
| Operating Temperature | -40°C to +85°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 95% Relative, Non-Condensing |
| Series Features |
| TAR Series |
| Series Description: Alternating Relay Motor Duplexor |
| Series Operation: ALTERNATING RELAY Upon application of power to the input terminals, nothing happens. When the control switch is closed, nothing happens. When the con- trol switch is opened, the output contact transfers causing LOAD A to de-energize and LOAD B to energize. When the control switch is re-closed, nothing happens. When the control switch is again opened, the output contact reverts to its original position, causing LOAD B to de-energize and LOAD A to re-energize. The system will continue to alternate in this sequence as long as power is applied. If the optional selection switch is set to either LOCK LOAD A or LOCK LOAD B, the corresponding load will be electrically locked ON and the alternating will cease while locked. Reset is accomplished by removal of input power. |
|