0.75mA maximum (60Hz, measured in conformance with UL, CSA, VDE)
Typical Efficiency
0.83
Overvoltage Protection
Outputs turns off at 105% (typical)
Voltage Adjustments
±10% (V.ADJ screw on top)
Output Holding Time
20ms minimum (at full rated input and output)
Rise Time
150ms max.
Line Regulation
0.4% maximum
Load Regulation
1.5% maximum
Fluctuation due to
Ambient Temperature
Change
0.05% maximum
Ripple Voltage
2% peak to peak maximum (including noise)
Overload Protection
120% typical, auto reset
Operation Indicator
LED (green)
Parallel Operation Allowed
Yes
Dielectric Strength
Between input and output terminals: 3,000V AC, 1 minute Between input terminal and housing: 2,000V AC, 1 minute Between output terminal and housing: 500V AC, 1 minute
Insulation Resistance
Between input and output terminals/input terminals and housing: 100M? minimum (500V DC megger)
Operating temperature
10 ? to +60 ?C (14 ? to 140 ?F) (see derating curves)
Operating humidity
20 to 90% relative humidity (no condensation)
Storage temperature
30 to +85°C (22 to +185°F)
Vibration resistance
10 to 50Hz, 0.75mm p-p, 2 hrs on each of 3 axes
Shock resistance
300m/s^(2) (30G), 3 shocks in each of 6 directions
Approvals
Conforms to EMC Directives EN50081-2 & EN50082-2. LVD Directive EN60529 Certified to EN60950. UL508 listed. UL, c-UL, TUV approved. CE marked. EN61000-3-2
Dimensions (mm) (terminal part except
120 x 200x 140
Weight (approx.)
2000g
Terminal screw (horizontal type)
Spring-up, fingersafe terminals with captive M3.5 screws
Series Features
PS5R Standard Series
Series Description:Switching Power Supplies
Wide power range: 7.5W-240W
Universal input : 7.5W-50W: 85-264V AC/105-370V DC 100W: 85-132V AC/170-264V AC; 240-370V DC (selectable); 75W, 120W, 240W: 85-264V AC/110-350V DC
Overcurrent/overvoltage protection
Power Factor Correction (75W, 120W, 240W models): EN61000-3-3; EN61000-3-2
Voltage adjustment +10%
Spring-up crew terminal, IP20 (finger-safe)
DIN rail or panel surface mount
Approvals: CE marked / UL 508 Listed UL, c-UL / TÜV approved EMC Directives: EN50081-2 EN50082-2 EN61000-6-2 LVD EN60950:2000