100 to 120V AC, 50/60Hz 200 to 240V AC, 50/60Hz (jumper selectable) 240 to 370V DC
Input Current (typical)
2.5A at 100V AC 1.5A at 200V AC
Internal Fuse Rating
4A
Inrush Current
50A maximum (at cold start at 200V AC)
Leakage Current (at
no load)
0.75mA maximum (60Hz, measured in conformance with UL, CSA, VDE)
Typical Efficiency
0.85
Overvoltage Protection
Outputs turns off at 105% (typical)
Voltage Adjustments
±10% (V.ADJ screw on top)
Output Holding Time
20ms minimum (at full rated input and output)
Rise Time
200ms maximum (at full rated input and output)
Line Regulation
0.4% maximum
Load Regulation
1.5% maximum
Fluctuation due to
Ambient Temperature
Change
0.05% maximum
Ripple Voltage
2% peak to peak maximum (including noise)
Overload Protection
120% typical, auto reset
Operation Indicator
LED (green)
Parallel Operation Allowed
No
Dielectric Strength
Between input and output terminals: 3,000V AC, 1 minute Between input terminal and housing: 2,000V AC, 1 minute Between output terminal and housing: 500V AC, 1 minute
Insulation Resistance
Between input and output terminals/input terminals and housing: 100M? minimum (500V DC megger)
Operating temperature
–10 ? to +60 ?C (14 ? to 140 ?F) (see derating curves)
Operating humidity
20 to 90% relative humidity (no condensation)
Storage temperature
–30 to +85°C (–22 to +185°F)
Vibration resistance
10 to 50Hz, 0.75mm p-p, 2 hrs on each of 3 axes
Shock resistance
300m/s^(2) (30G), 3 shocks in each of 6 directions
Approvals
Conforms to EMC Directives EN50081-2 & EN50082-2. LVD Directive EN60529 — Certified to EN60950. UL508 listed. UL, c-UL, TUV approved. CE marked. EN61000-3-2
Dimensions (mm) (terminal part except
75 x 145 x 95
Weight (approx.)
600g
Terminal screw (horizontal type)
Spring-up, fingersafe terminals with captive M3.5 screws
Series Features
PS5R Standard Series
Series Description:Switching Power Supplies
Wide power range: 7.5W-240W
Universal input : 7.5W-50W: 85-264V AC/105-370V DC 100W: 85-132V AC/170-264V AC; 240-370V DC (selectable); 75W, 120W, 240W: 85-264V AC/110-350V DC
Overcurrent/overvoltage protection
Power Factor Correction (75W, 120W, 240W models): EN61000-3-3; EN61000-3-2
Voltage adjustment +10%
Spring-up crew terminal, IP20 (finger-safe)
DIN rail or panel surface mount
Approvals: CE marked / UL 508 Listed UL, c-UL / TÜV approved EMC Directives: EN50081-2 EN50082-2 EN61000-6-2 LVD EN60950:2000