80kPa to 110kPa (Operating), 70kPa to 110kPa (Transport)
Reset Time
100msec maximum
Repeat Error
±0.2%, ±20msec*
Voltage Error
±0.2%, ±20msec*
Temperature Error
±0.5%, ±20msec*
Setting Error
±10% maximum
Insulation Resistance
100M? minimum (500V DC)
Dielectric Strength
Between power and output terminals: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole:1000V AC, 1 minute
Vibration Resistance
10 to 55Hz amplitude 0.5mm2 hours in each of 3 axes
Shock Resistance
Operating extremes: 98m/sec^(2) (10G) Damage limits: 490m/sec^(2) (50G) 3 times in each of 3 axes
Degree of Protection
IP40 (enclosure) (IEC60529)
Dimensions
RTE-P1, P2 40Hx 36W x 77.9D mm RTE-B1, B2 40Hx 36W x 74.9D mm
Weight (approx.)
RTE-P1: 87g / RTE-P2: 89g / RTE-B1, -B2: 85g
Series Features
RTE Multi-Function Timer
Series Description:The RTE series timers offer the most popular timing functions in 2 models (Power and Signal Triggered) together with high power 10A contacts. In fact, they use our famous RH2 relay, so you can be sure of the reliability.
Powered Triggered Models offer standard ON Delay, Interval and Cycle ON & OFF timing functions, while Signal Triggered Models offer 6 distinct timing functions. Both are tubular pin base or .187 quick connect terminals. All models mount into industry standard sockets or standard 45mm square panel cutouts using an optional adaptor.