| Manufacturer | IDEC |
| Manufacturer Product Number | NRBM3100-20A-AA |
| Description | Magnetic-Hydraulic Breaker; 20 A; 3-Pole; AA (AC, General Purpose) |
| Datasheet | Download Datasheet |
The IDEC NRBM3100-20A-AA is a 3-pole 20 A magnetic-hydraulic circuit protector with a lever actuator, rated 250V AC, 50/60 Hz and 65V DC. It is a UL 1077 supplementary protector, not for branch circuit protection.
It has IDEC's AA time-delay curve, the general-purpose curve common to molded-case breakers. All poles trip together and the levers are mechanically tied. The trip current does not drift with temperature; only the delay does.
Trip times at 25 °C: No trip at 100%; 15-120 s at 125%; 8-45 s at 150%; 3-15 s at 200%; 0.48-2.5 s at 400%. Interrupting rating: 1,000 A at 250V AC; 1,000 A at 65V DC. Terminals: main: M5 stud; auxiliary / alarm: 0.110 in quick-connect tab. Life: 10,000 operations minimum. It operates from -40 to +85 °C. Approvals: UL Recognized (UL 1077), cUL, VDE (EN 60934); UL file E68029.
| Category | |
| Manufacturer | IDEC |
| Model | NRBM |
| Current Rating (A) | 20 |
| Number of Poles | 3-Pole |
| Voltage Rating - AC | 250V AC, 50/60 Hz |
| Voltage Rating - DC | 65V DC |
| Interrupting Rating | 1,000 A at 250V AC; 1,000 A at 65V DC |
| Trip Curve | AA (AC, General Purpose) |
| Trip Characteristics | No trip at 100%; 15-120 s at 125%; 8-45 s at 150%; 3-15 s at 200%; 0.48-2.5 s at 400% (25 °C) |
| Inertia Delay | No |
| Internal Circuit | Series current trip |
| Actuator Type | Lever |
| Mounting Type | Panel Mount |
| Termination Style | Stud, M5 |
| Terminal Type | Main: M5 stud; auxiliary / alarm: 0.110 in quick-connect tab |
| Electrical Life (cycles) | 10,000 |
| Operating Temperature (°C) | -40...+85 |
| Approvals | UL Recognized (UL 1077), cUL, VDE (EN 60934) (E68029) |
| Standards | UL 1077, EN 60934 |