Product Description
Description: Three Phase Monitors (Voltage and Current) • Contact Configuration: 1C SPDT • Current rating:: 16 A • Supply/measured voltage:: AC 3× 190 – 500 V (50-60 Hz) • Mounting:: Panel • Time delay t0:: 2 s • Time delay t1:: adjustable, 1-300 s • Time delay t2: adjustable, 0.3-30 s
| Product Information | | Resources |
| Manufacturer | ELKO | | Product Category | Monitoring Relay | | Product Sub Category | Three Phase Monitors (Voltage and Current) | | Series | HRN3-70,PMR3-70 |
| | |
Product Attribute
| Attribute Value
|
| Contact Configuration | 1C SPDT |
| Current rating: | 16 A |
| Supply/measured voltage: | AC 3× 190 – 500 V (50-60 Hz) |
| Mounting: | Panel |
| Time delay t0: | 2 s |
| Time delay t1: | adjustable, 1-300 s |
| Time delay t2 | adjustable, 0.3-30 s |
| Breaking capacity: | 4000 A/AC1, 384 W/DC1 |
| Switching voltage: | 250 V AC/24 V DC |
| Power dissipation (max.): | 1.2W |
| Number of contacts: | 1× changeover (AgNi) |
| Mechanical life: | 10.000.000 ops. |
| Electrical life (AC1) | 100.000 ops. |
| Operating temperature: | -20 °C to 55 °C (-4 °F to 131 °F) |
| Storage temperature: | -30 °C to 70 °C (-22 °F to 158 °F) |
| Protection degree | IP40 from front panel/IP10 terminals |
| Standards: | EN 60255-1, EN 60255-26, EN 60255-27 |
| Supply terminals | 3-4-5 |
| Consumption (max.): | 2 VA/1 W |
| Level Umax: | 110 % Un |
| Level Umin: | 80 – 95 % Un |
| Hysteresis: | 0.05 |
| Asymmetry: | adjustable, 2–10 % Un + OFF |
| Max. permanent overload: | AC 3× 550 V |
| Peak overload <1ms: | NA |
| HRN3-70, PMR3-70 | |
| Series Description: Voltage monitoring relay in 3P with range switch |
- It is used for monitoring of voltage, power failure, sequence and asymmetry of phases in a 3-phase voltage system.
- Wide range of the monitored voltage with automatic selection of a lower/higher range.
- It measures actual voltage eff ective value - TRUE RMS.
- Fixed overvoltage level (Umax), adjustable undervoltage level (Umin).
- Adjustable time delay (t2) for elimination of short-time voltage peaks.
- Adjustable time delay (t1) after switching on or with a return from the faulty state.
- Adjustable asymmetry level with optional switching off .
- Reset of the error in the memory using a pushbutton on the panel or external opening contact.
|