Product Description
Description: Power Relays • Coil Voltage: 240 VAC • Contact Configuration : 6C 6PDT • Current : 5 Amps • Mounting : Bracket Mount • Operating Function : 2 Coil Latching
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Coil Voltage | 240 VAC |
Contact Configuration | 6C 6PDT |
Current | 5 Amps |
Mounting | Bracket Mount |
Operating Function | 2 Coil Latching |
Materials | 5 Amp: 1/8 Diameter Moveable Fine Silver|3/16 Diameter Stationary Fine Silver 10 Amp: 3/16 Diameter Moveable Silver Cadmium Oxide | 3/16 Diameter Stationary Fine Silver Gold Flash is Standard on all Contacts Gold Diffused Available on Special Order - Min. Qty. Reqd |
Expected Life | Electrical at Rated Load (Min.) 100,000 Operations | Mechanical Life 10,000,000 Operations |
Dielectric Strength | 800 VRMS, 60 Hz Between Contacts | 2200 VRMS, 60 Hz Between Other Elements |
Coil Voltages | AC: Up to 277 Volts/60 Hz | DC: Up to 125 Volts |
Coil Treatment | Molded Rynite® PET Std. Class F |
Insulation Resistance | 100 Megohms Minimum |
UL Insulation System File No. | E74443 S155D 155°C Total Temperature Std. (Covers S105 Class A and S130D Class B Requirements) |
Pick Up (at 25°C) | AC Volts 85% or Less of Nominal | DC Volts 75% or Less of Nominal |
Operate Time | Approx. 20 Milliseconds |
Release Time | Approx. 20 Milliseconds |
Operating Ambient | AC: -45° to 85° | DC: -45° to 100°C |
Coil Temperature Rise | (25°C Ambient - Continuous Duty) AC: 45°C Approx. @ 60Hz - Use at 50 Hz will cause slight increase in Coil Rise DC: 45°C Approx. |
Terminals | All versions pierced solder lugs |
Weight | All Versions Approx. 5.0 oz. (142 g) |
Series Features |
100ML Series General Purpose Magnetic Latching Relays |
Series Description: Magnetic latching relay that controls electrical loads |
|