Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Carlo Gavazzi |
| Manufacturer Product Number | DEA71DM24A030 |
| Description | Ground Fault Relay; 2 SPDT; DIN Rail |
| Datasheet | Download Datasheet |
The Carlo Gavazzi DEA71DM24A030 is a programmable 3-phase ground fault and power monitor for 24–240 V AC ±10%, 50–60 Hz ±10% systems. It warns and trips on ground-fault current of IΔn 300 mA (fixed); pickup Fixed 300 mA; max. continuous 5 x IΔn (continuous overload), read through an external CT Required: CTG035 / CTG050 / CTG070 / CTG120 / CTG160 / CTG210; sensor External core balance transformer (Carlo Gavazzi CTG family). It monitors earth leakage (residual current, Type A) via external core balance transformer; warning at 60% IΔn, alarm at 80% IΔn.
Trip delay: No delay; reaction time 215 ms. Display: Green LED ON (power), red LED AL (alarm), yellow LED PRE (warning). Accuracy: 10% of selected IΔn. Repeatability: 2% of selected IΔn.
Output: 2 SPDT, 5 A @ 250 V AC (AC1). Mounting: DIN Rail. Dimensions: 35.5 x 81 x 62.7 mm; width 35.5 mm. Power: < 2.5 VA. Approvals: cULus Listed (UL 508, CSA C22.2 No. 14-10).
| Category | |
| Manufacturer | Carlo Gavazzi |
| Model | DEA71 |
| Monitoring Function | Earth leakage (residual current, Type A) via external core balance transformer; warning at 60% IΔn, alarm at 80% IΔn |
| Ground Fault Current Range | IΔn 300 mA (fixed); pickup Fixed 300 mA; max. continuous 5 x IΔn (continuous overload) |
| Required Accessories | External CT Required: CTG035 / CTG050 / CTG070 / CTG120 / CTG160 / CTG210; sensor External core balance transformer (Carlo Gavazzi CTG family) |
| Number of Phases | 1-Phase |
| Input Voltage | 24–240 V AC ±10%, 50–60 Hz ±10% |
| Trip Delay | No delay; reaction time 215 ms |
| Status Indicator | Green LED ON (power), red LED AL (alarm), yellow LED PRE (warning) |
| Contact Configuration | 2 SPDT |
| Output Rating | 5 A @ 250 V AC (AC1) |
| Sensing Accuracy | 10% of selected IΔn |
| Repeatability | 2% of selected IΔn |
| Mounting Type | DIN Rail |
| Dimensions | 35.5 x 81 x 62.7 mm; width 35.5 mm |
| Protection Category | IP20 |
| Rated Power | < 2.5 VA |
| Operating Temperature (Storage) | -25…+60 °C (-40…+80 °C) |
| Electrical Life | 10^5 operations @ 250 V AC resistive load |
| Approvals | cULus Listed (UL 508, CSA C22.2 No. 14-10) |