Product Description
Description: Time Delay Relay • Interval • Input Voltage: 120 VAC • Timing Type: Fixed • Time Range: 900 sec • Mounting: Base Mount • Output Current: 1 Amp • Contact Configuration: NO • Fixed Timing Tolerance: 0.1
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 120 VAC |
Timing Type | Fixed |
Time Range | 900 sec |
Mounting | Base Mount |
Output Current | 1 Amp |
Contact Configuration | NO |
Fixed Timing Tolerance | 0.1 |
Operating Current | All voltages < 20 mA plus load current requirements. |
Timing Range Tolerance | Minimum time - 15% +0%, maximum time - 0% +15%. |
Timing Variation | ±15% of set point over specified temperature and voltage range. |
Repeatability Of Timing Period | ±1%nominal. |
Recycle Time | Operating voltage must be removed for a minimum of 200 milliseconds to guarantee all timing and output circuits have reset. |
Output Rating | Rated for 10mA to 1A inductive with inrush current to 25 A for 8 mS. |
Output Voltage Dropin "ON" State | 2V for DC models, 4V maximum for AC models. |
Leakage Current in "OFF" State | 1mA maximum for DC models, 3mA maximum for AC models. |
Transient Protection | Protected by silicon transient suppressors which respond to transients within 1 x 10-12 seconds to a peak pulse power dissipation of 1500 watts. |
Dielectric | 1500V rms all terminals to case. |
Operating Temperature | -20°C to +85°C. |
Humidity | 95% non-condensing. |
Construction | Encapsulated module with .25 quick connect wiring terminals. |
Agency Recognitions | UL File E47858: Appliance Controls-Component ATNZ2(US) &ANTZ8(Can), Auxiliary Devices - Component NKCR2 (US) & NKCR8 (Can). |
Series Features |
4300 Interval Timing Module |
Series Description: The model 4300 series provides a load circuit with operating voltage for a predetermined amount of time each time the operating voltage is applied. The operating voltage must be present for the duration that exceeds the preset interval timing period. The 4300 series is available in both AC and DC models and controls output load circuits to 1 ampere. Fixed or adjustable timing interval periods are available. Adjustable models have the interval time preset by adding a resistor across terminals 4 & 5. |