Low time: +0%, -50%, High time: -0%, +50%. Ex: Timing range -3, (2 - 1000 seconds), can range from 1 to 1500 seconds, with 2 - 1000 seconds as a guaranteed minimum range.
Repeatability Of Timing Periods
±2%
Timing/Temperature Coefficient
±0.25%/˚C
Dielectric
1,200V rms between open contact sets, 1,500V rms between contacts and operating voltage terminals.
Transient Protection
Protected by silicon transient suppressors responding to transients within 1x10-12 seconds to a peak pulse power dissipation of 1500 watts.
Operating Temperature
0˚C to +70˚C
Series Features
2300 Interval Timer
Series Description:The 2300 is an INTERVAL timer controlling a DPDT set of relay contacts. The 2300 is available in a range of both AC and DC models. When operating voltage is applied the output contacts energize for a preset timing period, and then de-energize. The output contacts will also de-energize if the operating voltage is removed prior to the end of the timing period. Two potentiometers provide timing adjustment over the useful timing range.