Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | Amperite |
| Manufacturer Product Number | 120AP10LC |
| Description | Time Delay Relay; 10 s; 120 V AC; DPDT (2 form C); 11 Pin Spade Terminal |
| Datasheet | Download Datasheet |
The Amperite 120AP10LC is a time delay relay with DPDT (2 form C) output and rated 10 A @ 240 V AC resistive; 15 A @ 30 V DC resistive; 15 A @ 120 V AC resistive; 1/3 HP @ 120 V AC; 1/2 HP @ 250 V AC, driven by a 120 V AC input.
It has a fixed delay of 10 s, set at the factory.
It is a Delay on operate (delay on make) timer.
Delay on operate timing cycle begins upon application of input power. The relay contacts transfer at the end of the delay period and will remain transferred until input voltage is removed. Reset occurs when input voltage is removed.
It has Plug-in (11-pin spade) mounting and 11 pin spade terminals.
| Category | |
| Manufacturer | Amperite |
| Part Status | Discontinued |
| Output Technology | Relay (electromechanical contacts) |
| Timing Circuit | Solid state analog |
| Timing Function | Delay on operate (delay on make) |
| Delay Time | 10 s |
| Timing Adjustment Method | Fixed (factory preset) |
| Contact Configuration | DPDT (2 form C) |
| Output Rating | 10 A @ 240 V AC resistive; 15 A @ 30 V DC resistive; 15 A @ 120 V AC resistive; 1/3 HP @ 120 V AC; 1/2 HP @ 250 V AC |
| Input Voltage | 120 V AC |
| Termination Style | 11 Pin Spade Terminal |
| Mounting Type | Plug-in (11-pin spade) |
| Enclosure | White plastic case; knob adjustable models have a dial scale for reference only; 'LC' version has a black case |
| Operating Temperature | -45...+70 °C (-60...+105 °C) |
| Approvals | UL (E96739 (M)), CSA (LR62586-3) |
| Setting Accuracy (%) | Fixed units: +/-5%; adjustable units: -0 to +25% of maximum specified delay time (minimum specified value or less at low end) |
| Repeatability (%) | +/-5% |
| Timing Cycle Interrupt Transfer | None |
| Mechanical Life | 10 million operations cycles (100,000 operations minimum at rated loads (@ 25 C) cycles) |
| Rated Power | AC units: 3 VA or less; DC units: 3 W or less |