Product Description
Description: Time Delay Relays • Delay on Break • Input Voltage: 115 VAC • Contact Configuration: 1C SPDT • Reset : Trigger Reset Function • Timing: Fixed • Time Range: 1 sec • Termination: .110 male electro-plate solder terminals • Current: 1 Amp
Product Information | Resources |
|
|
This product is Unavailable - the factory shut down on June 2023. Please Contact Customer Service for help with Cross Reference / Replacement |
Specifications |
Product Attribute | Attribute Value |
Input Voltage | 115 VAC |
Contact Configuration | 1C SPDT |
Reset | Trigger Reset Function |
Timing | Fixed |
Time Range | 1 sec |
Termination | .110 male electro-plate solder terminals |
Current | 1 Amp |
Temperature Range: Operating and storage: | Operating and storage: -25°C to +60°C, (-13°F to +140°F) |
Enclosure | Black plastic case |
Weight | 0.8 oz (23g) approx. |
Timing Adjustment | Knob adjustable potentiometer. |
Timing Tolerance | Fixed Units: ±5% |
Adjustable Units | -0 to +25% of maximum specified delay time. Minimum specified value or less at low end. |
Repeatability | ±5% |
Release Time | 60 ms typical, 100 ms maximum. |
Initial Dielectric Strength | Between open contacts: 500V RMS, Between contacts & coil: 500V RMS |
Power Requirement | AC units: 2 VA or less; DC units: 2 Watts or less |
Polarity Protection | On DC units - Yes. |
Series Features |
CR Series TDR |
Operation: Input voltage must be applied continuously to operate the internal relay. Relay contacts transfer when the trigger input terminal is activated. The timing cycle begins when the trigger input terminal is deactivated. When the timing cycle is completed the relay will de-energize. The timing cycle may be reset to zero during the timing cycle by reactivating the trigger input terminal. |
|