Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Mounting Type | Socketable |
Relay Type | Mechanical Relay |
Function | Repeat Cycle |
Circuit | DPDT (2 Form C) |
Delay Time | 1 Sec ~ 1023 Sec |
Contact Rating @ Voltage | 10A @ 250VAC/24VDC |
Voltage - Supply | 120VAC/DC |
Termination Style | Plug In, 8 Pin (Octal) |
Timing Adjustment Method | DIP Switches |
Timing Initiate Method | Input Voltage, Trigger Signal |
Series Features |
TBG Series Repeat Cycle-ON Time First DIP Switch TDR |
Series Description: When supply voltage is applied to the input, the relay energizes and ON time (T1) begins. Upon completion of the ON time, the relay de-energizes and the OFF time (T2) begins. Upon completion of the OFF time, the relay energizes and one cycle is complete. This ON/OFF cycling continues until supply voltage is removed from the input. The ON/OFF delay periods are independently selectable within the same range. |
|