| Product Attribute | Attribute Value |
| Type | Phase Loss, Phase Sequence, Voltage Sensing AC |
| Trip Status | Energized High/Low |
| Trip Range | 370 ~ 460V AC |
| Delay Time | 0.06 Sec~0.5 Sec |
| Voltage - Supply | 120VAC |
| Output Type | Relay |
| Circuit | DPDT (2 Form C) |
| Contact Rating @ Voltage | 3A @ 600VAC |
| Mounting Type | Chassis Mount |
| Series Features |
| SLE Series Phase Monitor |
| Series Description: The SLE Series Phase Monitor from the ATC Diversified Electronics division of Marsh Bellofram Corporation is designed to protect three-phase equipment against Phase Unbalance, Phase Loss, and Under Voltage. With normal operating voltage present on all three phases, the internal relay will energize (PICK-UP). When a phase loss occurs or the voltages fall outside the preset unbalance or under voltage settings, the internal relay will de-energize (DROP-OUT). The relay automatically resets when the line conditions return to normal. Both Delta and Wye systems may be monitored. In Wye Systems, connections to neutral are not required. NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLE series is designed to detect this condition when properly adjusted. |
|