Product Description
| 
 | 
| Product Information | Resources | 
| 
 | 
 | 
| Specifications | 
| Product Attribute | Attribute Value | 
| Type | Phase Loss, Phase Sequence, Voltage Sensing AC | 
| Trip Status | Energized High/Low | 
| Trip Range | 95 ~ 115V AC | 
| Delay Time | 0.06 Sec~0.5 Sec | 
| Voltage - Supply | 120VAC | 
| Output Type | Relay | 
| Circuit | DPDT (2 Form C) | 
| Contact Rating @ Voltage | 5A @ 240VAC | 
| Mounting Type | Chassis Mount | 
| Series Features | 
| SLE Series Phase Monitor | 
| Series Description: The SLE Series Phase Monitor from the ATC Diversified Electronics division of Marsh Bellofram Corporation is designed to protect three-phase equipment against Phase Unbalance, Phase Loss, and Under Voltage. With normal operating voltage present on all three phases, the internal relay will energize (PICK-UP). When a phase loss occurs or the voltages fall outside the preset unbalance or under voltage settings, the internal relay will de-energize (DROP-OUT). The relay automatically resets when the line conditions return to normal. Both Delta and Wye systems may be monitored. In Wye Systems, connections to neutral are not required. NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLE series is designed to detect this condition when properly adjusted. | 
| 
 | 
 
             
                         
            