Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Type | Phase Loss, Phase Sequence |
Trip Status | Energized High/Low |
Phase Unblance Range | 2%-10% adj |
Delay Time | 0.08 Sec ~ 0.7 Sec |
Voltage - Supply | 208/240VAC |
Output Type | Relay |
Circuit | DPDT (2 Form C) |
Contact Rating @ Voltage | 3A @ 240VAC |
Mounting Type | Chassis Mount |
Series Features |
SLC Series Phase Unbalance and Loss Monitor |
Series Description: The SLC Series Phase Unbalance and Loss Monitor from the ATC Diversified Electronics division of Marsh Bellofram Corporation is designed to protect 3-phase equipment against Phase Unbalance and Phase Loss conditions. With normal operating voltages applied to all three phases, the internal relay will remain de-energized (DROPPED-OUT). When a Phase Loss or Phase Unbalance exceeding the pre-selected trip point occurs, the relay will energize (PICK-UP). The SLC series is typically used in conjunction with a shunt trip breaker. Both Delta and Wye systems may be monitored. In Wye systems, connections to neutral are not required. NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLC series is designed to detect this condition when properly adjusted. |
|