Product Description
  | 
| Product Information | Resources | 
  | 
| Specifications | 
| Product Attribute | Attribute Value | 
| Type | Phase Loss, Phase Sequence | 
| Trip Status | Energized High/Low | 
| Phase Unblance Range | 2%-10% adj | 
| Delay Time | 0.08 Sec ~ 0.7 Sec | 
| Voltage - Supply | 120VAC | 
| Output Type | Relay | 
| Circuit | DPDT (2 Form C) | 
| Contact Rating @ Voltage | 3A @ 240VAC | 
| Mounting Type | Chassis Mount | 
| Series Features | 
| SLC Series Phase Unbalance and Loss Monitor | 
| Series Description: The SLC Series Phase Unbalance and Loss Monitor from the ATC Diversified Electronics division of Marsh Bellofram Corporation is designed to protect 3-phase equipment against Phase Unbalance and Phase Loss conditions. With normal operating voltages applied to all three phases, the internal relay will remain de-energized (DROPPED-OUT). When a Phase Loss or Phase Unbalance exceeding the pre-selected trip point occurs, the relay will energize (PICK-UP). The SLC series is typically used in conjunction with a shunt trip breaker. Both Delta and Wye systems may be monitored. In Wye systems, connections to neutral are not required. NOTE: When a phase is lost while the motor is running, a condition known as regeneration occurs where a voltage is induced into the open phase nearly equal in magnitude to the normal phase-to-phase voltage. The SLC series is designed to detect this condition when properly adjusted.  | 
  |