| Manufacturer | ATC Diversified |
| Manufacturer Product Number | SLA-240-AFA |
| Description | Phase Monitor Relay; 3-Phase; 240V AC (fixed); 1C SPDT |
| Datasheet | Download Datasheet |
The ATC Diversified SLA-240-AFA is a 3-phase monitor for 240 V AC (fixed) systems. It drops its output relay out on phase loss, phase reversal and undervoltage and resets once the fault clears.
Trip points: undervoltage 83% of nominal (one phase low); 90% of nominal (all three phases low). Adjustment: fixed, factory set. Trip delay: phase loss / reversal 0.5 s; undervoltage 0.5 s. Restart: 250 ms. Reset: automatic upon correction of the fault.
Output: 1C SPDT, 10 A resistive at 240 V AC; 345 VA inductive. Mounting: plug-in, on an 8-pin octal (RB-08 or OT-08 socket) base. Indicator: LED, glows when all conditions are normal. It operates from 0 to +55 °C and stores from -45 to +85 °C.
| Category | |
| Manufacturer | ATC Diversified |
| Model | SLA |
| Monitoring Function | Phase Loss, Phase Reversal and Undervoltage |
| Number of Phases | 3-Phase |
| Input Voltage | 240V AC (fixed) |
| Undervoltage Trip Range | 83% of nominal (one phase low); 90% of nominal (all three phases low) |
| Undervoltage Trip Adjustment | Fixed, factory set |
| Restart Delay (s) | 250 ms |
| Trip Delay - Phase Loss and Reversal (ms) | 0.5 s |
| Trip Delay - Undervoltage (s) | 0.5 s |
| Reset Method | Automatic upon correction of the fault |
| Status Indicator | LED, glows when all conditions are normal |
| Contact Configuration | 1C SPDT |
| Output Rating | 10 A resistive at 240 V AC; 345 VA inductive |
| Number of Poles | 1 |
| Mounting Type | Socketable |
| Termination Style | Plug In |
| Socket Family | 8 Pin Octal (RB-08 or OT-08 socket) |
| Operating Temperature (Storage) | 0...+55 °C (-45...+85 °C) |