Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | ATC Diversified |
| Manufacturer Product Number | SLA-208-AFA |
| Description | Phase Monitor Relay; 3-Phase; 208V AC (fixed); 1C SPDT |
| Datasheet | Download Datasheet |
The ATC Diversified SLA-208-AFA is a 3-phase monitor for 208 V AC (fixed) systems. It drops its output relay out on phase loss, phase reversal and undervoltage and resets once the fault clears.
Trip points: undervoltage 83% of nominal (one phase low); 90% of nominal (all three phases low). Adjustment: fixed, factory set. Trip delay: phase loss / reversal 0.5 s; undervoltage 0.5 s. Restart: 250 ms. Reset: automatic upon correction of the fault.
Output: 1C SPDT, 10 A resistive at 240 V AC; 345 VA inductive. Mounting: plug-in, on an 8-pin octal (RB-08 or OT-08 socket) base. Indicator: LED, glows when all conditions are normal. It operates from 0 to +55 °C and stores from -45 to +85 °C.
| Category | |
| Manufacturer | ATC Diversified |
| Model | SLA |