Product Description
|
| Product Information | Resources |
|
| Specifications |
| Product Attribute | Attribute Value |
| Type | Under/Over voltage per Phase |
| Trip Status | Energized High/Low |
| Trip Range | 400 ~ 560V AC |
| Delay Time | 0.1 Sec~0.5 Sec |
| Voltage - Supply | 480VAC |
| Output Type | Relay |
| Circuit | DPDT (2 Form C) |
| Contact Rating @ Voltage | 10A @ 240VAC |
| Mounting Type | Chassis Mount |
| Series Features |
| PBC Series 3-Phase Voltage Band Monitor |
| Series Description: The PBC Series 3-Phase Voltage Band Monitor from the ATC Diversified Electronics division of Marsh Bellofram Corporation offers protection to three-phase equipment that is required to operate between two voltage limits. All three phases are monitored individually for a pre-selected under and over voltage limit. With normal operating voltages applied, the internal relay will energize (PICK-UP). When the voltages on any or all phases fall outside the preset Over/Under trip points for longer than the Release delay, the relay will de-energize (DROP-OUT). When line conditions return to normal, the PBC Series Monitor automatically resets and the internal relay energizes. The LED fault indicators aid in set up and system trouble-shooting glowing on fault condition. The LED indicators have an immediate response to voltage conditions and operate independently of the relay. The HYSTERESIS in each unit provides a differential of 4% between the PICK-UP and DROP-OUT trip points. |
|