| Manufacturer | ATC Diversified |
| Manufacturer Product Number | MPA2-240-CT |
| Description | Phase Monitor Relay; OL/UL/PL/PR/Unbal/UV/OV; 3-Phase; 208/220/240V AC |
| Datasheet | Download Datasheet |
The ATC Diversified MPA2-240-CT is a 3-phase electronic motor overload relay for 208/220/240V AC motors drawing External CTs (CT30/5 to CT1000/5) full-load. It protects against overload, underload, phase loss, phase reversal, voltage and current unbalance, undervoltage and overvoltage, frequency, locked rotor. Built for: Motor protection analyzer: measures current, voltage, frequency, power factor, kW, kVA and kWh.
Low voltage threshold: -20% to -5% of rated voltage. High voltage threshold: +5% to +20% of rated voltage. Unbalance trip: 2-10% voltage unbalance; current unbalance above 48%. Overcurrent trip class: 5 to 30 (IEC 60255-8). Restart delays: 0-600 s after a voltage fault. Reset: Automatic or manual restart (programmable). Display: 16 x 2 LCD with current, voltage and load report; control and trip lights. Networking: Modbus RTU over RS485 (9600 baud).
Output: B300 pilot duty; 10 A general use at 277 V AC. Mounting: DIN Rail, surface or flush mount.
Approvals: cULus Listed, Industrial Control Equipment 496Y.
| Category | |
| Manufacturer | ATC Diversified |
| Model | MPA2 |
| Monitoring Function | Overload, Underload, Phase Loss, Phase Reversal, Voltage and Current Unbalance, Undervoltage and Overvoltage, Frequency, Locked Rotor |
| Special Application | Motor protection analyzer: measures current, voltage, frequency, power factor, kW, kVA and kWh |
| Number of Phases | 3-Phase |
| Input Voltage | 208/220/240V AC |
| Motor Full Load Current Range | External CTs (CT30/5 to CT1000/5) |
| Undervoltage Trip Range | -20% to -5% of rated voltage |
| Overvoltage Trip | +5% to +20% of rated voltage |
| Phase Unbalance Trip | 2-10% voltage unbalance; current unbalance above 48% |
| Overcurrent Trip Class | 5 to 30 (IEC 60255-8) |
| Restart Delay (s) | 0-600 s after a voltage fault |
| Trip Delay - Phase Loss and Reversal (ms) | under 1 s |
| Trip Delay - Undervoltage (s) | 1-30 s |
| Reset Method | Automatic or manual restart (programmable) |
| Status Indicator | 16 x 2 LCD with current, voltage and load report; control and trip lights |
| Communication Protocol | Modbus RTU over RS485 (9600 baud) |
| Output Rating | B300 pilot duty; 10 A general use at 277 V AC |
| Mounting Type | DIN Rail, surface or flush mount |
| Approvals | cULus Listed, Industrial Control Equipment 496Y |