Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | ATC Diversified |
| Manufacturer Product Number | GFD-100 |
| Description | Ground Fault Relay; 208-600V AC, phase to phase |
| Datasheet | Download Datasheet |
The ATC Diversified GFD-100 is a 3-phase ground fault display for 208-600 V AC, phase to phase systems. Wired across the three phases of an ungrounded system, its lights show at a glance when a phase has faulted to ground; it has no output relay.
Mounting: panel mount, vertical (1/4 in conduit adapter). Indicator: Three green LEDs normal, three red LEDs on a ground fault (flashing 2 per second). It operates from 0 to +55 °C and stores from -40 to +85 °C.
| Category | |
| Manufacturer | ATC Diversified |
| Model | GFD |
| Monitoring Function | Ground fault display for ungrounded 3-phase systems |
| Ground Fault Current Range | Detects 11.7 kΩ (50 Hz) / 9.3 kΩ (60 Hz) phase to ground, ±20% |
| Number of Phases | 3-Phase |
| Input Voltage | 208-600V AC, phase to phase |
| Frequency | 50/60 Hz |
| Status Indicator | Three green LEDs normal, three red LEDs on a ground fault (flashing 2 per second) |
| Mounting Type | Panel Mount, vertical (1/4 in conduit adapter) |
| Rated Power | 3 VA at 600 V AC |
| Operating Temperature (Storage) | 0...+55 °C (-40...+85 °C) |