Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | ATC Diversified |
| Manufacturer Product Number | UPA-100C |
| Description | Voltage Indicator |
| Datasheet | Download Datasheet |
The ATC Diversified UPA-100C is a voltage indicator: wired to the line side of a disconnect, its LEDs show from outside the closed panel whether any phase or stored DC energy is still present, before the door is opened.
Indicator: red LEDs, flash rate rises with voltage. AC range: 40-600 V AC, 50/60/400 Hz (line-to-line or line-to-ground). DC range: 30-1000 V DC. Maximum: 750 V AC / 1000 V DC. Detection threshold: 29 V AC 3-phase, 40 V AC single-phase, 27 V DC. Mounting: fits a 1-1/4 in conduit knockout. Leads: (4) 8 ft, 18 AWG 1000 V. Power: 1.2 W at 750 V AC. Enclosure: NEMA 4X, encapsulated. Approvals: cULus Listed (Ind. Cont. Eq. 496Y); CE; CSA. It operates from -20 to +55 °C and stores from -40 to +85 °C.
| Category | |
| Manufacturer | ATC Diversified |
| Product Type | Voltage indicator, conduit mount, CAT III / CAT IV |
| Indicator | Red LEDs, flash rate rises with voltage |
| Voltage Range AC | 40-600 V AC, 50/60/400 Hz (line-to-line or line-to-ground) |
| Voltage Range DC | 30-1000 V DC |
| Maximum Voltage | 750 V AC / 1000 V DC |
| Detection Threshold | 29 V AC 3-phase, 40 V AC single-phase, 27 V DC |
| Mounting Type | Fits a 1-1/4 in conduit knockout |
| Leads | (4) 8 ft, 18 AWG 1000 V |
| Power Consumption | 1.2 W at 750 V AC |
| Enclosure Rating | NEMA 4X, encapsulated |
| Operating Temperature | -20...+55 °C (-40...+85 °C) |
| Approvals | cULus Listed (Ind. Cont. Eq. 496Y); CE; CSA |