Get A Quote
My Account
To ensure accuracy, please note that images may be representative. Refer to the product data sheet for detailed specifications.
| Manufacturer | ATC Diversified |
| Manufacturer Product Number | VCFP96M |
| Description | Energy Meter |
| Datasheet | Download Datasheet |
The ATC Diversified VCFP96M is a 3-phase multifunction power meter for 5 A AC via CT (11 mA min, 6 A max).
It measures True RMS, covers 11-300 V AC phase-neutral; 19-519 V AC phase-phase and is accurate to Energy Class 1; voltage and current ±0.5% F.S.; power 1%; frequency ±0.1%; PF ±0.01.
It reports V (L-L / L-N), I1-I3, neutral current, frequency, PF, active / reactive / apparent power and energy, demand, %THD to 31st, phase sequence.
Primary programmable 1/5 A to 10 kA, secondary 1/5 A; PT primary 100 V-500 kV, secondary 100-500 V.
It communicates over RS-485 Modbus RTU (300-19,200 bps, address 1-255); pulse output 24 V DC max, 100 mA.
It runs on 100-240V AC, 50/60 Hz and mounts on panel Mount (96 x 96 mm; 91.5 x 91.5 mm cutout).
| Category | |
| Manufacturer | ATC Diversified |
| Meter Type | 3-phase multifunction power meter |
| Measurement Method | True RMS |
| Nominal Current | 5 A AC via CT (11 mA min, 6 A max) |
| Voltage Range | 11-300 V AC phase-neutral; 19-519 V AC phase-phase |
| Frequency Range | 45-65 Hz |
| Accuracy Class | Energy Class 1; voltage and current ±0.5% F.S.; power 1%; frequency ±0.1%; PF ±0.01 |
| Measured Values | V (L-L / L-N), I1-I3, neutral current, frequency, PF, active / reactive / apparent power and energy, demand, %THD to 31st, phase sequence |
| Current Sensing | External CT: primary programmable 1/5 A to 10 kA, secondary 1/5 A; PT primary 100 V-500 kV, secondary 100-500 V |
| Communication | RS-485 Modbus RTU (300-19,200 bps, address 1-255); pulse output 24 V DC max, 100 mA |
| Input Voltage | 100-240V AC, 50/60 Hz |
| Input Operating Range | -15% / +12% |
| Power Consumption | 8 VA max |
| Mounting Type | Panel Mount (96 x 96 mm; 91.5 x 91.5 mm cutout) |
| Wire Size | 0.5-2.5 mm²; 0.68-0.79 N·m |
| Operating Temperature (°C) | -10...+55 |
| Approvals | cULus Listed (E188860), CE; EMC IEC 61326-1 |