Product Description
|
Product Information | Resources |
|
|
Specifications |
Product Attribute | Attribute Value |
Type | Reversal, Loss, Unbalance, Under/Over Voltage |
Coil Voltage | 190-600 VAC |
Contact Configuration | 1C SPDT |
Mounting | Din Rail |
Contact Current | 5 Amps |
Comunication Platform | Modbus TCP |
Life | Electrical 100,000 closures @ full load; 360 operations per hour max. frequency; Mechanical: 30 million closures @ no load; 72,000 operations per hour max. frequency |
Temperature | Operating, -28o to 65oC (-18o to 149oF) Storage, -40o to 85oC (-40o to 185oF) |
Mounting | Mounts on 35mm DIN-rail or panel-mounted with two #8 screws when DIN-rail clips are fully extended from under the enclosure. |
Series Features |
PC SERIES WITH COMMUNICATION PHASE LOSS, PHASE REVERSAL, PHASE UNBALANCE,UNDERVOLTAGE & OVERVOLTAGE |
Series Description: PC Series Three-Phase Monitor Relays protect equipment from voltage faults and communicate via Modbus TCP. This industry-leading technology makes data available for continuous monitoring, real-time alerts and intelligent troubleshooting of voltage systems. Real-time data improves decision making within modern control systems. This affordable IoT solution is advantageous in automation applications requiring protection of valuable three-phase equipment within a “smart” connected control system. PC Series relays monitor three-phase system voltages to protect from damage due to phase loss, phase reversal, phase unbalance, undervoltage and overvoltage. These products detect single phasing, high, low and unbalanced voltages regardless of any regenerative voltages. Utilizing an advanced microprocessor-based design allows true RMS voltage measurement with full wave monitoring. This provides a more accurate method to measure the voltages, regardless of load type or wave shape. True RMS voltage measurement ensures accurate sensing in most generator and other applications with non-sinusoidal wave forms, eliminating nuisance tripping. A universal monitored voltage range of 190 to 600V AC covers more global applications. Dials allow adjustment of the undervoltage trip point, trip delay, restart delay, unbalance trip point, and selection of Line-to-Line system voltage. A 60 mm wide enclosure meets IEC Standards and mounts on 35 mm DIN-rail or on a panel with two screws inserted through extended clips on the back of the enclosure. Pluggable terminal blocks on both the input and output side allow for easy installation and replacement, without having to remove any wires. |
Operation: Pluggable terminal blocks simplify initial wiring and replacement |
|